Arrived to system off, checked pressures and found system completely out of R22. Found indoor blower wheel dirty and outdoor capacitor out of range 45/5 reading 29/1.6. Due to age of equipment and amount of repairs recommended a comfort advisor to come out and give quote to upgrade system. Tried scheduling a comfort advisor however homeowner said she would not be available until next week. She stated she would reach out to us to set up appointment. System is currently turned off at breaker to prevent further damage.