I discover the evaporator coil thermal expansion valve is stock causing a restriction on the refrigerant line. Also found the upstairs filter is dirty and needs to be replaced. We installed a new oem TXV valve and pulled a evacuation on the refrigerant lines to 500 microns. Release charge and tested operations everything is working properly at this time on the upstairs system.