Found the control board was burnt which was causing the blower motor to run constantly. Determined the main drain was either backing up causing water to overflow through the furnace reaching the electrically the coil could have frozen up due to a plugged filter not changed since last year. Installed new control board and told customer to keep an eye out to make sure water dries up otherwise we may need to replace drain line, did treat drain pan with tablets to help break up any debri. Also found capacitor for blower motor out of tolerance as well as igniter out of tolerance. Tested heating and cooling after work was completed, good refrigerant charge, dual capacitor on ac is ok but might be out of tolerance by next year. No other issues or concerns at this time other than age of equipment and ac running on R22 which is being phased out by 2020.