Have any feedback for us? We'd love to hear it! Call us at (405) 883-4058 and let us know how we are doing.
Downstairs ac Condenser trane repairs not needed 1.2 rla condenser fan 13.3 rla compressor 246 volts ac R410a refrigerant txv 123 psi suction 16.8 degrees subcooling 42 degree vapor saturation temp 322 psi high side pressure 11.7 subcooling 101.5 bubble saturation temp 59.7 mfd / 4.97 mfd capacitor rated at 60/5 mfd 440 vac