4771 N Franklin Rd
Indianapolis, IN 46226
317-577-8077

Job Locations
for noblesville, in


Map of Noblesville IN
Jacob R.

Jacob R.


Job Checkin

System tripping hpco in both first and second stage heat pump operation. Manually drived eev open and pressures dropped. Suction line transducer jumping on ohm reading after running for a while. Last check had sensor at .3ohms and 95psig, for that pressure level, ohm reading should be at 1.4ohms. Ordered new transducer and temp sensor. Recommend adding surge protection to condenser