Jacob was very knowledgeable and helpful. One of the best service providers I've come across! We will definitely use Family again.
Christian called me 15-20 minutes before he arrived as I had requested. He was courteous and professional. Upon completion of the preventive maintenance service he went over things with me to answer any questions I had.
Very punctual and courteous. Everything is explained very well.
Very nice Young Man very informative and a pleasure to be around
Tyler was very respectful and responsive to my questions and even inquired about codes for CO discharge
Disappointed. Very very over priced they changed their original quote from a little over 3000 to 12,000 would not recommend this company
Thank you for installing a new furnace today! You guys are always great😄
Tyler did an awesome job fixing our furnace was very polite and professional
Installed whole home air purifier for both upstairs and downstairs systems. Www.airscrubberbyaerus.com for more detailed product information. Provided estimate for membership to perform cleaning on both systems. If you have any questions feel free to reach out, 4632379511
B1 Clean & Check Service Garage furnace Blower motor is leaking oil. It also doesn’t have a filter slot, so it currently doesn’t have a filter. Furnace is working at this time. Basement Furnace Blower wheel has some buildup on blades. Filter slot doesn’t have a good seal and sucking air from basement. The transition box on the Supply side has Come apart and a new one needs to be installed. Also the high voltage and low voltage need to be installed correctly.
Performed maintenance on 90 percent furnace. Cleaned condensate trap of debris as well as flushed lines. Cleared pressure switch hose lines. Checked gas pressure in both stages, both testing within factory range, changed filter upon customer request, checked amp draws of inducer as well as blower, both tested well within range, check blower for debris on wheel, found very little. Igniter and flame sensor both checked within factory range, burners were clear of debris, electrical wiring was secure. Furnace operates well at this time
Everything is working well at this time.
Replaced smashed ductwork supply run with R8 insulated flex duct, verified proper airflow
Performed basic maintenance on 90 percent furnace, checked blower and inducer for amp draws and both were in factory range, checked filter, checked blower for buildup, blower looked clean and was functional, checked gas pressure which was within factory range, removed condensate trap and cleaned thoroughly. Tested flame sensor and igniter, both tested well, check burners for buildup and found none. System is running well at this time.
Performed heating tuneup, this is first visit on new contract. Serviced accuclean and bypass humidifier. System is functioning properly at this time. Mightyducts or rescueduct for ductcleaning
Duct design is all messed up. Units are mix matches and undersized. Matt is going to come out tomorrow to quote mini splits and redesigning duct.
Humidistat was satisfied at 35%. Customer was complaining about static throughout the house. I increase the setting to 45% humidity and set the thermostat to circulate mode. Found no other issues.
Cracked heat exchanger. Will quote repair vs replacement.
Upon arrival, system was intermittently having combustion vary from first 4 burners to all. When only 4 would ignite, ignition would fail at flame rectification. Gas pressure is within range but there is alot of rust and condensation around gas valve and throughout combustion area. Pulled burners and found corrosion around all burners. Cleaned out to make flame transfer smoother. Cycled system 15x, full combustion occurred across all burners everytime- hesitated on 3rd fire and 12th fire (burner 4to5) but pushed through. If issue occurs again, recommend replacing burner assembly. HSi Is also very close to failure but currently operational. Replaced hsi and purchased membership
B2 Clean & Check Service Cleaned and Tested heating system. The supply trunk above the coil has a lot of growth and it spreading through the duct work. Customer also wants a quote on moving some vents for a remodel.
Customer has had power fluctuations recently, another company came out over the weekend due to blower not operating properly. System was operating properly upon arrival with no faults. Suspect power cycling fixed previous issue. Tested operation in heat pump and auxillary modes. Recommend installing surge protection on outdoor unit and on controlboard leg of incoming for air handler.
Performed maintenance on 90 percent furnace, checked amp pulls of blower and inducer, both within factory specs at time of tune up. Inducer capacitor is also within range, burners are clean and free of debris, removed flame sensor and cleaned, as well as check ignition system, which tested within factory range. Pulled and cleaned condensate trap, as well as flushed condensate lines and inspected pressure switch tubing. Filter looked decent, gas pressure tested within range in first and second stage. Temperature rise between return and supple also tested within factory range, inspected all wiring for any faults, none found at this time.
B1 Clean & Check Service Cleaned and Tested heating system. Everything is working well at this time.