Danny B.

Danny B.


Job Checkin

No AC, found secondary drain pan full of water tripped float switch, removed water, checked main drain pan found it to be rusted and cracked which caused water to leak into secondary pan, also found blower motor constantly running, removed low voltage wiring from board to see if blower motor would shut down, but it did not, tested voltage at board and found short at the relay which is causing the blower to constantly run.