Noah  D.

Noah D.


Job Checkin

Arrived and found a slight leak from the relief valve. The boiler is at 17 psi while at 180 degrees. It is not over pressurizing. While I was here previously I remember the backflow had been clogged due to the water quality. Having this poor of water quality is going to damage a lot of the water components on the boiler. The water feeder is very clogged and barely feeds water which was mentioned last visit. Replaced the water feeder and the relief valve. All other components look okay at this time. Recommended to have the customer get a water quality test and see if the water softener is operating properly or there will be other issues like this in the future. Tested the system operation after repairs. The system is operational at his time.