850 U.S. 9
Fishkill, NY 12524
845-896-4328

Job Locations
for new paltz, ny


Map of New Paltz NY
Noah  D.

Noah D.


Job Checkin

Upon arrival the customer said the condenser would stay running even with the thermostat off. Turned he system on and checked pressures. They are normal. Turned it off and the system stayed running. Opened the electrical door to check the components. Found the contactor pulled in even with no 24 volts there. Tapped on it and it opened. The contactor was very burnt and chard. Replace under warranty and tested the system.