850 U.S. 9
Fishkill, NY 12524
845-896-4328

Job Locations
for poughkeepsie, ny


Map of Poughkeepsie NY
Brandon G.

Brandon G.


Job Checkin

Upon arrival found second floor zone not heating. Went down to boiler and found second floor air bound and circulator pump not running. Also found air vent leaking and expansion tank water logged. Replaced water components and purged all three zones. All three zones pipes came back hot.