Brandon G.

Brandon G.


Job Checkin

Upon arrival found boiler in hard lockout. Reset tripped primary control and system ran for 5 minutes and shut down in lockout. Found cad cell eye discolored and ignition transformer warped. Replaced both components and system fired. Adjusted air band to drop running ohms and performed combustion test.