Arrived to inspect system not cooling. The downstairs system was running but not cooling. Upon inspection I found the system to almost be completely out of refrigerant. Operating pressure at 17 psi and standing pressure of 66 psi. The leak is visible on the back side of the outdoor unit. Also checked compressor and it is only pulling 2 amps and rated for 15. Checked capacitor on outdoor unit as well and it is bad. Going to set up a lead time for comfort advisor to come out and go over options. System not operating properly upon departure.