Arrived on no cooling, turned system on all came on working, checked refrigerant levels, motor controllers, amps and ohms on compressor. Checked all three windings on compressor herm and start are good but run was bad. Outdoor fan rla 1.4>1.31 Compressor rla 16.4>8.78 Capacitor mfd 45/5>45/4.9 Suction psi 100 Liquid psi 250 Temp split supply 66 return 80 Upon diagnostic found the compressor to be the issue due to pressures and temperatures being off and ohms bad on run side. Due to age, cost of repairs plus uses r-22 refrigerant had supervisor give estimate on new system with full 10-years warranty vs repair options that we do not recommend.