Customer stated that the cooling is still insufficient. We evacuated the r-410a from the system and leak tested with nitrogen before doing a full nitrogen sweep. We added the factory charge of 11lbs. 12 oz. And ran the unit. We adjusted the charge to 8 degrees of sub cooling. The supply registers are blowing 50 degree air. Do use Ted with pics. The customer was not available to sign.