Troubleshot Lennox ML14XC1 not cooling. Found refrigerant leak at Schrader valve. Recovered remaining R-410A. Replaced faulty Schrader core using Ritchie Yellow Jacket core removal tool. Pressure tested system with nitrogen. Evacuated to 250 microns. Recharged with factory-specified 7.1 lbs of R-410A. Tested operation.