Customer said coil was icing over. Found filter was plugged off, blower motor capacitor was out of range causing the blower to not start, and the system was low on refrigerant. Changed filter. Changed blower motor capacitor. And recharged system with r22. Watched system run for 30 minutes. Everything is running as it should. Temp drop of 17 degrees. Confirmed operation of system.