Upon arrival system was cooling fine. Customer was saying that one day the inside unit was working only and not the outside unit. I checked all the electrical components on the outside unit and found capacitor is good and contactor. Condenser unit has a hard start that is not working at all. I checked amps and system is not over amping but I still recommended customer to replace it. I checked pressures and everything was looking good. Replaced the hard start and customer paid $445.50 total with card