Today we visited because the AC was not working. The drain line was backed up and this triggered the float switch and turned the unit off. If this issue continues we should consider eliminating the p-trap at the air handler because the unit has a trap where the drain goes under the building foundation.

Today we visited because the AC was not working. 

The drain line was backed up and this triggered the float switch and turned the unit off. 

If this issue continues we should consider eliminating the p-trap at the air handler because the unit has a trap where the drain goes under the building foundation.