Found systems suction line icing up. System low on refrigerant. Recovered refrigerant and found leak at flare of suction line at evaporator. Cut and flared fitting and tightened up. Pressure tested with nitrogen. Pulled vacuum and charged to specs with new refrigerant. Reran primary line. Found that system has a condensate pump inside for secondary line. Ran new secondary line for it. Redid platform so it was not crushing electrical. Redid disconnect box and vulcumed around lineset seal. Leveled out condenser that had bad slope to it on roof.