Return to perform quoted repair of installing hard start kit to lower lock rotor amps below manufacture specifications check system before down system is drawing 120 A installed hard start kit and checked operation of system found system is now only pulling 91 Amps system is operating properly Customer was concerned about an error message popping up on the thermostat about the auxiliary heat running for too long verify that refrigerant level is OK verify that condensing unit operates properly verified temperature rise in heat mode down system is operating properly.