Performed diagnostic on a 2017 Lennox Heatpump split system. Upon arrival found system was completely flat on refrigerant, customer approved to perform nitrogen leak test. Found leak at refrigerant lines section between attic and ceiling are met. Give estimate for lines replacement, system evacuation, and add refrigerant to spec. Emailed customer the invoices.