05JUL2023 Jason Brown Arrived for 2022 install not cooling well. Spoke with Kendra about the systems performance. Our daughter has been living in the room beneath the upstairs equipment and that room has struggled with keeping up, so when we had your company replace the upstairs equipment we had them run an extra supply to her room downstairs. She has since moved out and we are finding the upstairs struggling to achieve the temperature desired. We are keeping the upstairs at 80 degrees until we are ready to use the room. Inspected air handler, and ductwork Found blower speed set to 700 CFM found supply ductwork to be an 8” 10” and 12”. Coil is clean, air temperature 56-57 at registers. Found second floor to be supplied by one 12” flexible duct. That supply splits 4 times once above the second floor. Today I Closed dampers to downstairs and upstairs landing. This is to force more air to the 12” run suppling the upstairs. I also set the blower speed to 1000 CFM. I recommend we increas