Tom M. 1-16-25. 3 system blue shield maintenance. One gas furnace, two air handlers no heat pumps. System #1 gas furnace. Cleaned flame sensor. Blower motor bearings are good. Set gas pressure in first and second stage. Flue Co 10 ppm. Idm amps .9 noticed igniter is in poor condition uploaded a photo recommend replacing the part. System #2 Upstairs Air handler. Tightened all electrical connections. Blower capacitor 4.7 rated for 5. Blower bearings are good. System has 1 heat strip. It’s operating pulling 2.4 amps. Evaporator coil is in poor condition due to heavy rust accumulation at the bottom. System #3 Guest house. Found breaker off to the air handler which is located outside. Tightened electrical connections. Blower motor bearings are good. Both heat strips are operating pulling 20 maps. I turned the breaker back off how I found it. Customer will call in to schedule the igniter repair if he wants to move forward. I’ve also explained 410a phase and that the new system are going t