12-30-24 Isaac J. Came out to call for a system not heating properly. Customer stated that the heat pump kept shutting off and coming back on without completing a full heating cycle, so they turned it off. I checked the system overall and found the unit faulting on high pressure due to a bad blower motor. Discussed with customer about repair needed. System is still under warranty until June of 2025. Customer approved warranty repair and picking up part. Let customer know that it was going to be available tomorrow. 12-31-24 Came back out to replace blower motor. Pulled blower assembly and took existing motor out. Installed new blower motor in bracket and installed it into the assembly. Reinstalled assembly back into air handler, wired motor in and cycled unit in all modes on thermostat to confirm system as operating properly. Discussed with customer about maintenance plan for unit, but they aren’t interested at this time. Still recommend unit be serviced next spring. System is now oper