Blue shield club AC maintenance. Joe(JC)R. 07/23/2024 Performed full system evaluation and safety inspection. I arrived to perform the customer’s annual AC maintenance. The customer said that everything was running well and that they wanted the system to be checked out one last time before they move out of state. I washed out the condenser then checked the furnace and evaporator coil. The furnace and coil were in good shape and the drain pan and line were both clear and in good shape. I then checked the condenser. When checking out the condenser I found that the condenser capacitor was getting weak. This was causing the compressor to pull higher than normal amps and placing extra strain on the compressor. The rest of the condenser was in good shape and running well. I received permission from the customer to replace the capacitor. After replacing the capacitor I reinspected the condenser and found that everything was running well. The system is running well at this time.