Today I had the pleasure of conducting a 1 time air conditioning tune up on a 5 year old Goodman systems. Upon arrival, the homeowner stated that they had just bought the home and they wanted to address some of the concerns the inspector found and to get an overall evaluation on how the system was doing. The first thing they showed me is that there is no proper location for the filter to be used for the return. The existing filter was in the furnace directly under the blower assembly. They showed me the return vent that was in a coat closet nearest the furnace but didn’t have a filter vent. I recommended a filter cabinet be installed under the furnace for ease of access. I then verified system cleanliness and found the blower assembly and ducts were dirty and in dire need of cleaning. I then verified all amps temps and pressures and found the system inrush (LRA) out of manufacturer specifications. It is not to exceed 77 amps but I read it at 82.4 amps. I recommend adding a hard start k