Joseph K.

Joseph K.


Job Checkin

Jake Kring. 12-06-24. I arrived for a previous customer system won’t stop heating when the stat satisfies. I inspected the system with the homeowner and found the thermostat is using batteries but the thermostat is wired to run with the power of the system. We found the furnace to be dirty and the blower cap to be weak. I recommended to replace the capacitor to keep the motor running properly and to keep the proper power going to the blower motor when it cycles on and stays running. The homeowner decided to have me replace the capacitor at this time. We cleaned the system and checked all electrical components and gas pressures with the combustion readings. We found the gas pressure to be set at 2.8 IWC and the system calls for 3.2-3.8 IWC. We set the gas pressure to 3.5 IWC and let the system run and cycle off on its own to confirm that the system will cycle on and off on its own. Once the system satisfied to 68 deg we found the thermostat room temperature rose to 69 degrees as the fur