Jake Kring. 02-10-25. I arrived for a blue club membership fall tune up. I spoke with the tenant and format the system has been heating well but he has two filters in need of replacing. I replaced both 14X24X1 pleated filters and checked the furnace operation. I found the evaporator coil to be clean but extremely rusted and toy can see part of the coil fins through the front of the coil due to how bad the coil is rusted. I also found the induced draft motor to be starting really slow before it can catch up to speed and allow the pressure switch to close and cycle the furnace on. I informed the tenant of the systems condition and due to the systems age and how it’s running I would expect some repairs to a cure but I would replace the system vs making extensive repairs.