Joseph K.

Joseph K.


Job Checkin

I arrived for a non member no cool call. I first inspected the system located in the garage closet and found the system to be running properly. I inspected the condenser and found the coils to be compressor stopped up. I checked all electrical components and found no issues. I check the system refrigerant charge and found the the system to be running low on R410A. I recommend to preform a leak search to find the leak and see what we needed to do to fix the leaking area or component. The homeowner declined to just add what refegerant was was necessary to get the system running properly. I cleaned and added 5LBS 2OZ of R410A to the system and set the systems subcooling at 12 deg. I told the homeowner that they will have this problem again if the leak is not found and fixed. This system is running to the best of its abilities at this time.