27AUG2024 Jason Brown Arrived for new customer not cooling well. Spoke with homeowner about the systems performance. I have a 2 year old dual head Fujitsu mini split system, the head units don’t feel like they’re cooling as well as they used to. The bedroom mini split head drips water, and the living room doesn’t seem to keep up. I had someone out to tune them up 3 months ago, however I’m unsure that he did a good job. Inspected equipment cycled both heads into powerful cooling. Waited 15 min then tested temperatures. Both are putting out about 52-56 degree air. Ran equipment for 30 mins cooled the room about 3 degrees. Inspected drains. Found both drains ran without a French drain, and the back systems drain clogged up. Inspected blower wheels and found them to be dirty. Discussed findings with homeowner. We decided to move forward with 2 blower wheel cleanings in place, and 2 French drains. Systems are cooling, back system is still not draining properly.