Tom M. 11-21-24 no heat. Customer stated the air handler is tripping the 30 amp breaker and there’s an electrical smell. All three heat strips are pulling 21 amps, blower motor runs fine pulling 2.2. After the emergency heat runs it trips the 30 amp breaker. There a strong electrical smell concentrated around the breaker panel not the air handler. Customer is going to contact an electrician to have the breaker checked out.