Joseph K.

Joseph K.


Job Checkin

I arrived for a non member no cool call. I first spoke with the tenant and found the main issue to be the outdoor system will not run. I inspected the condenser and found the condenser fan motor to be running between 1.28-1.39 amps. This condenser fan motor is not raited to run more than 1.30 amps. This motors surfaced temp was 184 deg. I checked the contactor, duel run capacitor and the hard start kit and found no issues. I checked the system refegerant charge and for the subcontinent to be running at 10.4 deg and the systems calls for 12 deg subcooling. I strongly recommend to replace the condenser fan motor before it completely fails. The tenant is to get ahold of the homeowners and get approval for the recommended repair. This system is 17 years old. I recommend to start planning on replacing the system due to age.