11/21/2024 JeremiahF Arrived on site and went over scope of today’s service. Recovered refrigerant and uninstalled existing equipment. Flushed line set. Installed new equipment. Made duct board transition from furnace to slab coil. Sealed with metal tape. Return duct is directly attached the the bottom pan of the furnace which was sealed with mastic. Installed new float switch on coil and wired with existing auxiliary drain float switch. Pressure checked line set at 250 psi and passed pressure test. Pulled vacuum down to 130 microns and passed vacuum decay. Released refrigerant, will need to go back out to verify charge on a later day when outdoor ambient temp is high enough to properly check. Set gas pressures for both stages of heating. System is operating properly at this time.