Blower amps in emergency heat mode. 4.44 amps/6.8 Compressor amps 12.4 amps/18.3 Condencer fan amps 1.4 amps/2.8 Compressor capacitor 58.7 / 60 range 56.4-63.6 Jake Kring. 02-25-25. I arrived for a previous customer system inspection on the heater and air conditioning system. I first inspected the heat and found the system to have undersized duct work with a high static pressure. This system is a 4 ton system with 20 KW of heat. One heat strip is open electrically. This heat strip could have burnt in two due to the low airflow and the excess heat the system is producing. I also inspected the ac and checked all electrical components and refrigerant charge and found the system to be a R22 system but the refrigerant charge is just about perfect at this time. The systems evaporator coil is extremely rusted and I did inform the homeowner of the issue with trying to remove the coil to clean the system. The blower and evaporator coil are dirty and we discussed the systems biological grow