23JAN2024 Jason Brown Arrived for multi system inspection. Spoke with George upon arrival and he informed me that one of the unit heaters was currently not operating. We decided to get an estimate for that repair while out. Inspected 7 split systems and 2 unit heaters. Found all split systems in good condition and working properly. Ran systems for ~ 15 min each checked over ductwork and components at the furnaces. One unit heaters is working well, the other had the power switch off. Found the board to have been recently replaced. Cycled power and checked through circuits found high limit partially open. This is preventing the gas valve and ignition from coming on. Attached is the estimate for repair. #5 reception #3 lobby #4 North East offices #7 South East offices #6 Central rooms and some common areas #2 Northwest offices. #1 South west offices Unit heater a south attic Unit heater b north attic