4 systems blue shield club heater maintenance. Joe(JC)R. 10/24/2024 Performed full system evaluation and safety inspection. I arrived to perform the customers’s annual Heater maintenance. The customer didn’t have any questions and said that systems were operating correctly. They did mention that the filters dropped loudly when the equipment stopped running. I told the customer if they purchased foam furniture pads that they could be used to keep them from making as much noise. I then checked the furnaces. The heat exchangers were in good shape along with heater components. I found that the unit in the outdoor closet has as weak capacitor. It’s at 11.6MFD and is rated for 12.5MFD. This will cause extra wear and tear on the blower motor. The capacitor will eventually fail and can cause damage to the blower motor. The system in the other outdoor closet next to the newer system also has a weak capacitor. It’s at 13.5MFD and is rated for 15. I also replaced the filters for the customer.