21FEB2025 Jason Brown Arrived for silver club two system tune up. Spoke with Victor about the systems performance. He explained that the downstairs system is not keeping up like it used to, and that the upstairs system is working well. We inspected the downstairs system and found one heat strip not on. Adjusted wire over to other sequencer and everything worked. Cycled heating and checked through all operations, verifying amp draws and heat rise. Found this system to be heating properly. Inspected upstairs system found system has no service disconnect at the air handler. Verified cap while under load, checked all amps and electrical connections, found evap and blower wheel both ready to be cleaned. Spoke with Victor about my findings and we decided to leave it be for now. Both systems are heating at this time. Thanks!