Taylor P.

Taylor P.


Job Checkin

Arrived to the home due to the furnace not heating properly. Was greeted by the customer at the front door where I was shown where the furnace and thermostat were located. Customer said the furnace wasn’t working at all. I started looking at the 1998 Carrier furnace and noticed the furnace was locked out on “high limit lockout”, so I started looking at possible reasons why the high limit could be tripped and found a few issues. Found that blower motor was out of balance, also found that system only has 1-14” return which is not enough return for proper operation of the furnace and air conditioning, also the high limit it’s self is slightly weak as well. I reset the unit and tried to higher the fan speed to move more air but it still would trip limit, only could get furnace to run for about 2 min and 30 second before limit would trip out again. Explained to the customer my findings and discussed replacement vs and repair, we both decided it would be in his best interest to get some