Tom M. 1-16-25 Silver club furnace maintenance. Air filter is clean will need to be changed in the spring. 16x25x4. Cleaned flame sensor, blower capacitor 7.7 rated for 7.5. Blower motor bearings are good. Set gas pressure to 3.5 inwc. Idm amps .6. Flue Co is good 30 ppm. Inspected the heat exchanger noticed no issues. Advised the customer the system is past it’s typical life expectancy and recommended upgrading when the system has a failure. System is heating properly at this time.