Blue shield club AC maintenance. Joe(JC)R. 08/14/2024 Performed full system evaluation and safety inspection. I arrived to perform the customer’s annual AC maintenance. The customer didn’t have any questions and said that everything was running well. I then washed out the condenser and inspected it. I found that the condenser capacitor was getting weak on both sides. The fan side was at 6.8MFD and is rated for 7.5MFD. The compressor side was at 36MFd and calls for 40MFD. I then inspected the air handler. The blower motor capacitor was starting to get weak and was at 22MFD and calls for 25MFD. The capacitors that are weak will eventually fail and cause damage to the components they are connected to. As they get weak they will place extra stain on the parts they are connected to. The customer wants to wait to replace the parts.