-Replaced 30A Square D circuit breaker at heat pump outdoor disconnect with 25A Square D per unit data tag. Outdoor disconnect heavily corroded. Inspector may require replacement of internal cover or entire disconnect, per his/her discretion. Line side wiring not protected at entrance to back of disconnect. -Verified crawl space air handler “on unit” breaker sized appropriately as 60A per unit data tag. Replace wiring from sub panel to disconnect and disconnect to air handler. Replaced disconnect. Replace 40A square D breaker with 60A Square D breaker. Rewire low voltage wiring as appropriate. -Observed water leak near kitchen location in crawl space. Pictures/video attached to job. Recommend initiating plumbing service call.