Found 20 ton condenser not running upon arrival. Cycled power found circuit #2 suction pressures low at 67PSI and continuously fluctuating within -10PSI. Added R410a for diagnostic purposes and found faulty OD TXV is not metering correctly. Built and sent estimate for repairs. Field supervisor will be reaching out with full replacement cost before a decision is made. Darren is person of contact.