—Performed CMA Inspection on 2 Gas Package Systems and 2 Wall Mount Package Heat Pumps. -Gas Package 1 - 2012 Goodman: Main (Right) Building: No obtainable reading from outdoor fan motor side of dual run capacitor. Recommend installing 5 mfd capacitor for outdoor fan motor. Provided estimate for capacitor. Compressor failed megohm test at last maintenance. This indicates that insulation on motor winding has deteriorated and that the compressor may be due for failure. Due to age of system and likelihood of compressor failure, replacement of system should be considered. -Wall Mount 1 - 2009 Bard 2 Ton Package Heat Pump: Classroom Building, Left Side from Front: Compressor failed megohm test at last maintenance. This indicates that insulation on motor winding has deteriorated and that the compressor may be due for failure. Due to age of system and likelihood of compressor failure, replacement of system should be considered. -All systems operating at this time. Wall Unit 1 and Gas Pack