Upon arrival tech found condenser 3 in a hard lockout due to multiple low pressure lockouts. Tech reset system and found suction pressure immediately drops upon startup. Tech inspected air handler and found blower not running. Tested module and found it to be receiving 240v as well as a 24v call. Motor and module have failed. Need to order motor and module and schedule repair.