- Tech found tripped 30A electric furnace breaker in sub panel upon arrival. System was replaced in March; first time operating heat. - Furnace breaker is 60A, drawing 44.8 from the 30A breaker in the sub panel, causing it to overheat and trip. - Tech received approval and upsized sub panel breaker to 60A and confirmed proper system operation with 20 minutes of run time using heat strips. - Customer invested in a monthly premium service agreement for one split system heat pump. Customer is interested in improving indoor air quality. Tech installed two 16x20x1 filters on A-frame coil. System is operating normally at this time.