PERFORMED CMA FULL SERVICE ON 8 SPLIT SYSTEMS. SPLIT SYSTEM #4 DUAL RUN CAPACITOR RATED 70/7.5mf TESTED WEAK ON COMPRESSOR SIDE AT 67.9mf. CAPACITOR DUE FOR FAILURE. RECOMMEND REPLACEMENT OF CAPACITOR. REPLACEMENT OF DUAL RUN CAPACITOR 70/7.5mf WOULD BE. ALL OTHER SYSTEMS ARE PERFORMING PROPERLY. PERFORMANCE REPORT AND PICTURES ARE ATTACHED TO THIS INVOICE.