Tech preformed CMA INSPECTION on 7 Split Systems, 7 Mini Split Systems and 1 Window Unit. Split System #4 ( kitchen) is still down due to compressor being shorted to ground, issue was found during previous CMA Visit. Tech recommends replacing System. Split System #5 ( front nurses station) is operating but has multiple challenges such as leaking evaporator coil, weak fan capacitor, compressor failed megohm test and now compressor is shutting down intermittently due to thermal overload on compressor. Tech recommends replacing System. Split System #1 ( dining room) does operate but thermostat is faulty not allowing system to activate. Tech recommends replacing thermostat. Split System #6 ( front lobby) does operate but found with weak fan capacitor, tech recommends replacing capacitor. Mini Split Systems #2, #5, #6 & #7 do operate with the E.O.S. Tech was unable to locate remotes to control systems to confirm proper operation. Tech recommends purchasing remote controls or installing the