PERFORMED CMA FULL SERVICE ON 5 GAS PACKAGE SYSTEMS. UPON ARRIVAL TECH WAS MADE AWARE THAT GAS PACKAGE #4 IS NOT OPERATING AT THIS TIME. THERE WAS NO POWER TO SYSTEM OR THERMOSTAT, TECH ASKED CUSTOMER WOULD THEY LIKE SOME OPTIONS FOR REPLACEMENT OF SYSTEM AND CUSTOMER STATED THEY WOULD NOT WANT ANY OPTIONS FOR REPLACEMENT OF SYSTEM. GAS PACKAGE #1 IS PERFORMING PROPERLY IN COOL MODE AND HEAT MODE AND HAS NO CHALLENGES AT THIS TIME. GAS PACKAGE #3 IS HEATING PROPERLY BUT FAN DOES NOT RUN IN COOL MODE CAUSING SYSTEM NOT TO COOL PROPERLY. SYSTEM HAS A FAN CAPACITOR RATED FOR 10mf THAT TESTED AT 0.00mf. FAN CAPACITOR HAS FAILED CAUSING FAN TO NOT OPERATE, RECOMMEND REPLACEMENT OF FAN CAPACITOR FOR GAS PACKAGE #2, THERE IS AN ESTIMATE PROVIDED FOR REPLACEMENT OF FAN CAPACITOR. GAS PACKAGE #2 HAD A 15 mf CAPACITOR INSIDE OF ELECTRICAL PANEL THAT WAS HOOKED UP TO OLD FAN MOTOR, CAPACITOR IS NOT IN USE BUT ALSO TESTED LOW AT 6.12mf. GAS PACKAGE #2 FAN CAPACITOR RATED FOR 15mf TESTED WEAK AT 7.