-Performed CMA Full Service on 12 Split Systems and 2 dehumidifiers at 6 different buildings on site. -Building E System - 2014 Goodman 5 Ton Split: Dual run capacitor tested weak. Recommend replacement of 80/5 mfd dual run capacitor. Provided estimate. -Building F System - 2006 Goodman 5 Ton Split: Outdoor fan motor amperage at FLA limit. Motor pulling high amperage and may be due for failure. Recommend replacing motor. Provided estimate. Blower motor pulling excessive amperage. Likely a result of very weak capacitor. Motor is in danger of shorting if capacitor is not replaced. Provided estimate for replacement of capacitor. -Building G System 1 - 1999 Copeland 3 Ton R22 Split: Observed call on thermostat wires but not at contactor. System is void of refrigerant and would need a leak search performed, repair and recharge of refrigerant to operate. Provided estimate for charging system with nitrogen and performing leak search. Observed contactor arching when engaged. Recommend repl