Upon arrival tech was informed air handler was running none stop even when thermostat was satisfied. Inspected system and found the air handler relay board J5-4 had a green wire coming from it going to the thermostat and condenser G wire causing a constant 24v call. Tech removed wire and blower cycled on when there is a call and cycled off when satisfied. System is back operational at this time.